Content
During a routine temperature-rise test, a 2000 A switchboard failed because its main busbar reached 112 K above ambient - 7 K over the limit. The conductor size had been copied from an earlier design that ran cooler. The difference was not the load; it was the heat balance set by enclosure ventilation, material choice, and conductor shape.
Temperature rise controls the continuous rating of a busbar, the life of its insulation, and the safety of bolted joints. This article explains the busbar temperature rise calculation from the heat balance, shows a 2000 A design example, and summarizes the limits in IEC 61439-1 and UL 891.
At steady state, a busbar reaches a stable temperature when the heat generated by its own resistance equals the heat rejected to the surroundings. In short: a busbar has no single fixed rating; it has a temperature rise curve that changes with the cooling environment.
The generated heat is Joule heating: Q_gen = I² × R_ac.
The rejected heat leaves by convection and radiation: Q_diss = h × S × ΔT + ε × σ × S × (Ts4 - Ta4).
For design work, both loss paths are combined into an equivalent coefficient h, giving:
ΔT = (I² × R_ac) / (h × S)
where:
The relationship is quadratic: if current doubles, losses quadruple. A bar that stays cool at 800 A can overheat at 1250 A in the same cubicle.
Temperature rise vs current for a 160 × 10 mm copper bar
For quick estimation, engineers rearrange the heat balance into ampacity form:
I = K × √(A × ΔT)
where A is the cross-section in mm², ΔT is the allowable rise in K, and K is an empirical constant that bundles resistivity, surface finish, and ventilation. The minimum section is:
A = I² / (K² × ΔT)
| Arrangement | Copper (K) | Aluminium (K) |
|---|---|---|
| Single bar in free air | 11-13 | 8.5-10 |
| Bar in a ventilated enclosure | 9-11 | 7-8.5 |
| Bar in a sealed or unventilated enclosure | 7-9 | 5.5-7 |
Treat these constants as a starting point. A final design must be verified by calculation or type test, especially in compact assemblies.
Size a 2000 A LV distribution board busbar with an allowable rise of 40 K inside a ventilated enclosure.
For copper in a ventilated enclosure, take K = 8.5 (mid-range).
A = 2000² / (8.5² × 40) = 4,000,000 / 2890 = 1384 mm²
A 160 × 10 mm bar gives 1600 mm², about 16% above the minimum. A 125 × 12 mm bar (1500 mm²) also fits many panel layouts.
ΔT = (2000 / 8.5)² / 1600 = 34.6 K, below the 40 K limit. At 2400 A the same bar rises to 49.8 K - over the limit. The last 20% of current adds about 44% more temperature rise.
Material choice changes K and therefore the physical section. Aluminium has about 64% higher resistivity than copper, so it needs roughly 1.6 to 1.7 times the cross-section for the same current and rise. In return it weighs about 70% less, which reduces support loads and can offset the larger section price in long runs.
| Property | Copper | Aluminium |
|---|---|---|
| Resistivity at 20 °C (Ω·mm²/m) | 0.0172 | 0.0282 |
| Temperature coefficient (1/K) | 0.00393 | 0.00403 |
| Relative ampacity at same cross-section | 1.00 | ~0.78 |
| Cross-section needed for same ampacity | baseline | ~1.6x |
| Weight for the same ampacity | baseline | ~50% less |
For the 2000 A, 40 K example, aluminium needs about 2367 mm², typically two 100 × 12 mm bars per phase. Aluminium joints also need careful surface preparation because the surface oxide film adds contact resistance and creates hot spots.
Required cross-section for 2000 A at 40 K rise
Magnesium-Aluminum Alloy Tubular Busbar for High-Voltage StationsThis tubular busbar line covers multiple alloys and voltage classes up to 1000 kV, making it a practical choice when sizing conductors for high-current outdoor substations where thermal limits and mechanical strength both matter.View Product →
Aluminium is also common as tube conductor in outdoor substations. The thermal logic is the same, but a tube has less cooling surface per unit cross-section than a flat bar, so selecting the right aluminium alloy tubular busbar starts with the allowable temperature rise and then considers mechanical strength.
At 50/60 Hz, AC resistance exceeds DC resistance because current crowds toward the surface. A wide thin bar such as 160 × 10 mm has a better AC-to-DC ratio than a 50 × 32 mm bar of the same section, since more material stays near the cooling surface.
Keep the width-to-thickness ratio above 10:1 where possible. For multiple bars per phase, space them by at least one bar thickness so each surface can dissipate heat.
Most switchgear specifications cite IEC 61439-1 or UL 891. Both verify temperature rise on the assembled product, not on the bare conductor. The values below are the commonly used limits; the contract edition of the standard takes precedence.
| Standard | Component | Typical limit |
|---|---|---|
| IEC 61439-1 | Terminals for external conductors | 70 K |
| IEC 61439-1 | Bare copper internal connections | 105 K |
| IEC 61439-1 | Bare aluminium internal connections | 90 K |
| UL 891 | Main busbars in a switchboard | 65 K |
When the conductor is insulated, the rise limit drops because the insulation material has a maximum continuous operating temperature. The check then targets the hot spot at the conductor-insulation interface, and the insulation thickness becomes part of the thermal resistance.
Epoxy Resin Cast Tubular Busbar with Integrated InsulationThis product's one-shot molded insulation and shielding address the hotspot at the conductor-insulation interface; its long-life, flame-retardant structure suits applications where continuous conductor temperature and surface temperature both need verification.View Product →
Fully insulated tubular busbars therefore need two checks: conductor temperature and outer surface temperature. For short-circuit conditions, this continuous calculation does not apply - use the adiabatic equation for fault withstand instead.
Use ΔT = (I/K)²/A or the heat balance ΔT = I²R/(hS), then compare the result with the applicable standard limit for the component.
IEC 61439-1 commonly allows 105 K for bare copper internal connections; UL 891 is stricter for switchboard busbars at 65 K. Insulated conductors follow the insulation temperature class instead.
With the same cross-section and current, yes. Aluminium needs about 1.6 times the copper cross-section to reach the same steady-state temperature rise.
Use the maximum specified ambient, usually 35 °C or 40 °C. The conductor temperature equals ambient plus the calculated rise, and both must stay within the material or insulation limit.
Busbar temperature rise calculation is not academic. It decides whether a switchboard passes its type test, whether a busway carries its nameplate current on a hot afternoon, and whether insulation ages prematurely. Calculate at the highest credible current, apply a realistic enclosure derating, and pick a conductor whose material and cross-section match the thermal environment.
When the application involves high currents or limited space, a manufacturer with type-tested busbar and busway products can supply both the hardware and the supporting thermal documentation.